Combination fuse lightning arrester 11kV-100
11kV-100
Describe:The disconnector switch is a device used to isolate a power supply in an electrical system. It is usually used to ensure that electrical equipment can be safely cut off in case of maintenance, overhaul or emergency. The disconnector is usually operated with a rotatable handle or pull rod so that the operator can easily turn on or off the circuit.
Characteristic(FUSE CUTOUT):
Rated voltage:11kV
Rated current:100A
Impulse withstand voltage to earth:110kV
Creepage distance:410mm
Characteristic(ARRESTER):
Rated voltage:11kV
Nominal discharge current:10A
Max.continuous operating voltage(MCOV):9.4kV
Creepage distance:390mm
Characteristic(FUSE CUTOUT):
Rated voltage:11kV
Rated current:100A
Impulse withstand voltage to earth:110kV
Creepage distance:410mm
Characteristic(ARRESTER):
Rated voltage:11kV
Nominal discharge current:10A
Max.continuous operating voltage(MCOV):9.4kV
Creepage distance:390mm
Quantity
| Electrical Characteristics | Specification | Unit |
| FUSE CUTOUT | ||
| Rated Voltage | 11 | kV |
| Rated current | 100 | A |
| Breaking current | 8 | kA |
| Impulse withstand voltage (BIL) | 110 | kV |
| Power frequeney withstand voltage | 45 | kV |
| Creepage distance | 410 | mm |
| Standard | IEC60282-2 | / |
| ARRESTER | ||
| Rated Voltage | 11 | kV |
| Nominal discharge current | 10 | kA |
| Max.continuous operating voltage(MCOV) | 9.4 | kV |
| Creepage distance | 390 | mm |
| Standard | IEC60099-4 | / |