Composite Line post Insulator FZS-66-17
FZS-66-17
Describe:This product is applied to high voltage power line service. And have features of good hydrophobicity , anti-ageing, anti-leakage trace and electric erode proof, tensile strength and bending strength, strong mechanical, shock resistance good quake proof and brittle failure proof, light weight, easy to installation.
Characteristic:
Voltage:66kV
Maximum design load of the cantilever: 17kN
Creepage distance:2346mm
Standard:IEC-61952
Characteristic:
Voltage:66kV
Maximum design load of the cantilever: 17kN
Creepage distance:2346mm
Standard:IEC-61952
Quantity
| Electrical Characteristics | Specification | Unit |
| Rated Voltage | 66 | kV |
| Frequency | 60 | Hz |
| Maximum design load of the cantilever | 17 | kN |
| Creepage distance | 2346 | mm |
| Structure height | 940±20 | mm |
| Dry arcing Distance | 718 | mm |
| Lightning impulse withstand voltage | 410 | kV |
| Wet Power Frequency Wthstand Voltage | 260 | kV |
| Dry Power Frequency Wthstand Voltage | 330 | kV |
| Standard | IEC-61952 | / |