FUSED ISOLATION SWITCH RGW-27-630
RGW-27-630
Describe:Ceramic disconnecting switches are usually used in high voltage or special environment, and their main function is to provide safety and reliability protection when the circuit is interrupted or isolated power supply. This kind of switch is made of ceramic material, with good insulation performance and high temperature resistance characteristics, usually used for requiring corrosion resistance, high pressure resistance, long life occasions.
Characteristic:
Rated voltage:15kV
Rated Current:630A(Disconnector) 100A(Fuse cutout)
Lightning impluse withstand voltage:85kV
Leakage distance:460mm
Characteristic:
Rated voltage:15kV
Rated Current:630A(Disconnector) 100A(Fuse cutout)
Lightning impluse withstand voltage:85kV
Leakage distance:460mm
Quantity
| Electrical Characteristics | Specification | Unit |
| Rated Voltage | 15 | kV |
| Frequency | 50 | Hz |
| Rated Current | ||
| Disconnector | 630 | A |
| Fuse cutout | 100 | A |
| Rated breaking Current(Fuse) | 25 | kA |
| Rated peak making currents(Fuse) | 50 | kA |
| Short time withstand current(3 sec) | 25 | kA |
| Power-Frequency withstand voltage (Wet) | 30 | kV |
| Lightning impluse withstand voltage | 85 | kV |
| Leakage distance | 460 | mm |
| Standard | IEC62217-105 | / |